Uninterruptible Power Systems (UPS)

Systems from 30KVA-750KVA

 
Powerware 9315

Powerware Selection Guide

Family Brochure

   

Powerware 9315, 30-80KVA

Input

 

Voltage Range

Frequency Range

(60Hz) 57-64HZ
(50Hz) 47-53Hz

Surge Protection

Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2

Power Factor

0.95 Typical at full load

Output

 

Voltage Regulation

Better than +/- 1%

Voltage THD

Less than 5% (100% nonlinear load); Less than 3% (100% linear load)

Transient Response

Less than 5% for 100% load, step full recovery within 1 cycle

Frequency Regulation

(Free Run) +/- 0.005 Hz

Frequency Sync Range

+/- 0.5 Hz

Frequency Slew Rate

1 Hz/sec.

Load Crest Ratio

3:1

Powerware 9315, 100-160KVA

Input

 

Voltage Range

 

Frequency Range

(60Hz) 57-64HZ
(50Hz) 47-53Hz

Surge Protection

Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2

Power Factor 0.95 Typical at full load

Output

 

Voltage Regulation

Better than +/- 1%

Voltage THD

Less than 5% (100% nonlinear load); Less than 3% (100% linear load)

Transient Response

Less than 5% for 100% load, step full recovery within 1 cycle

Frequency Regulation (Free Run) +/- 0.005 Hz
Frequency Sync Range +/- 0.5 Hz
Frequency Slew Rate 1 Hz/sec.
Load Crest Ratio 3:1

Powerware 9315, 200-300KVA

Input

 

Voltage Range

 

Frequency Range

(60Hz) 57-64HZ
(50Hz) 47-53Hz

Surge Protection

Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2

Power Factor 0.95 Typical at full load

Output

 

Voltage Regulation

Better than +/- 1%

Voltage THD

Less than 5% (100% nonlinear load); Less than 3% (100% linear load)

Transient Response

Less than 5% for 100% load, step full recovery within 1 cycle

Frequency Regulation (Free Run) +/- 0.005 Hz
Frequency Sync Range +/- 0.5 Hz
Frequency Slew Rate 1 Hz/sec.
Load Crest Ratio 3:1

Powerware 9315, 400-500KVA

Input

 

Voltage Range

Frequency Range

(60Hz) 57-64HZ

Surge Protection

Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2

Power Factor 0.95 Typical at full load

Output

 

Voltage Regulation

Better than +/- 1%

Voltage THD

Less than 5% (100% nonlinear load);
Less than 3% (100% linear load)

Transient Response

Less than 5% for 100% load, step full recovery within 1 cycle

Frequency Regulation (Free Run) +/- 0.005 Hz
Frequency Sync Range +/- 0.5 Hz
Frequency Slew Rate 1 Hz/sec.
Load Crest Ratio 3:1

Powerware 9315, 625-750KVA

Input

 

Voltage Range

+10% to -15%

Frequency Range

+/-5%

Surge Protection

Meets ANSI C62.41, Category A & B, EN 50091-2 and EN 50082-2

Power Factor  0.85 Typical at full load
Output  

Voltage Regulation

Better than +/- 1%

Voltage THD

Less than 5% (100% nonlinear load); Less than 3% (100% linear load)

Transient Response

Less than 5% for 100% load, step full recovery within 1 cycle

Frequency Regulation (Free Run) +/- 0.005 Hz
Frequency Sync Range +/- 0.5 Hz
Frequency Slew Rate 1 Hz/sec.
Load Crest Ratio 3:1