Uninterruptible
Power Systems (UPS)
Systems
from 30KVA-750KVA |
|
|
| Powerware 9315 |
Powerware Selection Guide |
|
Family Brochure |
|
|
|
|
|
Powerware 9315, 30-80KVA
|
Input
|
|
|
Voltage Range
|
|
|
Frequency Range
|
(60Hz) 57-64HZ
(50Hz) 47-53Hz
|
|
Surge Protection
|
Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2
|
|
Power Factor
|
0.95 Typical at full load
|
|
Output
|
|
|
Voltage Regulation
|
Better than +/- 1%
|
|
Voltage THD
|
Less than 5% (100% nonlinear load); Less than 3% (100% linear load)
|
|
Transient Response
|
Less than 5% for 100% load, step full recovery within 1 cycle
|
|
Frequency Regulation
|
(Free Run) +/- 0.005 Hz
|
|
Frequency Sync Range
|
+/- 0.5 Hz
|
|
Frequency Slew Rate
|
1 Hz/sec.
|
|
Load Crest Ratio
|
3:1
|
|
|
 |
|
|
|
Powerware 9315, 100-160KVA
|
Input
|
|
|
Voltage Range
|
|
|
Frequency Range
|
(60Hz) 57-64HZ
(50Hz) 47-53Hz
|
|
Surge Protection
|
Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2
|
|
Power Factor |
0.95 Typical at full load |
|
Output
|
|
|
Voltage Regulation
|
Better than +/- 1%
|
|
Voltage THD
|
Less than 5% (100% nonlinear load); Less than 3% (100% linear load)
|
|
Transient Response
|
Less than 5% for 100% load, step full recovery within 1 cycle
|
|
Frequency Regulation |
(Free Run) +/- 0.005 Hz |
|
Frequency Sync Range |
+/- 0.5 Hz |
|
Frequency Slew Rate |
1 Hz/sec. |
|
Load Crest Ratio |
3:1 |
|
|
 |
|
|
|
Powerware 9315, 200-300KVA
|
Input
|
|
|
Voltage Range
|
|
|
Frequency Range
|
(60Hz) 57-64HZ
(50Hz) 47-53Hz
|
|
Surge Protection
|
Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2
|
|
Power Factor |
0.95 Typical at full load |
|
Output
|
|
|
Voltage Regulation
|
Better than +/- 1%
|
|
Voltage THD
|
Less than 5% (100% nonlinear load); Less than 3% (100% linear load)
|
|
Transient Response
|
Less than 5% for 100% load, step full recovery within 1 cycle
|
|
Frequency Regulation |
(Free Run) +/- 0.005 Hz |
|
Frequency Sync Range |
+/- 0.5 Hz |
|
Frequency Slew Rate |
1 Hz/sec. |
|
Load Crest Ratio |
3:1 |
|
|
 |
|
|
|
Powerware 9315, 400-500KVA
|
Input
|
|
|
Voltage Range
|
|
|
Frequency Range
|
(60Hz) 57-64HZ
|
|
Surge Protection
|
Meets ANSI C62.41, Category A & B
EN 50091-2 and EN50082-2
|
|
Power Factor |
0.95 Typical at full load |
|
Output
|
|
|
Voltage Regulation
|
Better than +/- 1%
|
|
Voltage THD
|
Less than 5% (100% nonlinear load);
Less than 3% (100% linear load)
|
|
Transient Response
|
Less than 5% for 100% load, step full recovery within 1 cycle
|
|
Frequency Regulation |
(Free Run) +/- 0.005 Hz |
|
Frequency Sync Range |
+/- 0.5 Hz |
|
Frequency Slew Rate |
1 Hz/sec. |
|
Load Crest Ratio |
3:1 |
|
|
 |
|
|
|
Powerware 9315, 625-750KVA
|
Input
|
|
|
Voltage Range
|
+10% to -15%
|
|
Frequency Range
|
+/-5%
|
|
Surge Protection
|
Meets ANSI C62.41, Category A & B, EN 50091-2 and EN 50082-2
|
|
Power Factor |
0.85 Typical at full load |
|
Output |
|
|
Voltage Regulation
|
Better than +/- 1%
|
|
Voltage THD
|
Less than 5% (100% nonlinear load); Less than 3% (100% linear load)
|
|
Transient Response
|
Less than 5% for 100% load, step full recovery within 1 cycle
|
|
Frequency Regulation |
(Free Run) +/- 0.005 Hz |
|
Frequency Sync Range |
+/- 0.5 Hz |
|
Frequency Slew Rate |
1 Hz/sec. |
|
Load Crest Ratio |
3:1 |
|
|
 |
|
|